PERIODIC TESTING OF EMERGENCY AND EXIT LIGHTS
PERIODIC TESTING OF EMERGENCY AND EXIT LIGHTS
INTRODUCTION
Emergency and exit lights provide illumination for safe exit during power outages.
Fermilab has approximately 4000 emergency lights in 330 buildings and enclosures.
Fermilab uses a testing program to assure proper light function during emergencies.
Divisions/Sections are responsible for assuring that emergency and exit lights in areas
for which they have landlord responsibility are tested periodically according to the
procedure outlined below.
Emergency lights are to be tested on a monthly and annual basis as described below.
Exit lights are to be tested monthly as described below. Those exit lights powered by
an Uninterruptible Power Supply (UPS) are to be tested on an annual basis as well.
REFERENCE
NFPA 101-7.9, Emergency Lighting National Fire Protection Association 101 Life
Safety Code, 2003 ed.
NFPA 101-7.8, 7.10, Exit Lighting Emergency Lighting National Fire Protection
Association 101 Life Safety Code, 2003 ed.
PROCEDURE
Tests
a. Monthly Tests. All emergency/exit lights shall be tested monthly for at
least 30 seconds by activation of the test mechanism, unplugging the
unit, or activating the local circuit breaker. The light passes the test if it
emits a plainly visible light for the duration of the test.
b. Annual Tests. All emergency lights (and appropriate exit lights) shall be
tested annually by activation of the test mechanism or unplugging the
unit for at least 90 minutes. The light passes the test if it emits a plainly
visible light at the end of the test.
c. Exception. Emergency lighting units located in beamlines generally
inaccessible to personnel due to beamline operation are exempted from
the requirements of 1.a and 1.b above. Units in such areas shall be tested
as follows:
(i) Operating Periods (Generally inaccessible to personnel) - no
testing required.
(ii) Shutdown Periods (Generally accessible to qualified personnel),
Duration of Less Than 10 Days - no testing required.
(iii) Shutdown Periods, Duration of 10 Days to 30 Days - one-30
second test during the shutdown period.
(iv) Shutdown Periods, Duration of 30 Days to 1 Year - one 90 minute
test during the shutdown period and 30 second tests at 30 day
intervals for the duration of the shutdown period.
(v) Shutdown Periods, Duration Greater Than 1 Year - follow the
requirements of 1.a and 1.b above.
Read More....!
Download for Free on Marine Notes Online
Buy Online via Secure Paypal or Fill Order Form for Alternative.
2 comments:
Great information about Emergency Lights, Your information is really informative for us.......
Emergency Lighting Requirements
Emergency lighting provides the illumination that enables people to see clearly, to avoid obstacles and to be able to move faster and more confidently to the nearest exit and to safety in a crisis.
Emergency Lights
Post a Comment
Thanks for your visit.